Overview

CISA published advisory ICSA-26-307-01 on 3 November 2026 for Subnet Solutions PowerSYSTEM Center, a product from the Canadian vendor Subnet Solutions Inc. CISA lists the affected sectors as Critical Manufacturing and Energy, with worldwide deployment. The advisory describes two vulnerabilities: an incorrect-authorization flaw and a SQL injection flaw in the report designer.

This article is based on the CISA advisory alone. We did not open the vendor’s own bulletin or the NVD records for either CVE, so scores and version ranges below are CISA’s. We could not confirm whether the scores are CISA-assigned or come from the CNA, and the NVD API returned no record for either CVE when we checked on 4 November 2026.

The two vulnerabilities

CVECWESummary (per CISA)CVSS v3.1CVSS v4.0
CVE-2026-63017CWE-863 Incorrect AuthorizationA low-privileged, authenticated user can access resources normally limited to administrators9.0 Critical9.4 Critical
CVE-2026-63774CWE-89 SQL InjectionInsufficient input validation in the report designer lets an authenticated user execute unauthorized SQL commands9.0 Critical9.4 Critical

Both carry the same vectors: CVSS:3.1/AV:A/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H and CVSS:4.0/AV:A/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H.

Reading the vector: the attack vector is Adjacent (AV:A), meaning the attacker needs to reach the product from the same network segment or a similar adjacent position. Privileges required are Low (PR:L), so a valid account of any kind is enough. No user interaction is needed, and scope is Changed (S:C), which is why the score reaches 9.0 despite the adjacent vector.

CISA also states that “these vulnerabilities are not exploitable remotely.” That is consistent with the adjacent vector: an attacker needs network-level proximity and credentials. It does not mean the risk is low for sites where engineering or operator networks are broadly reachable.

Affected versions and fixes

CISA’s summary lists these affected ranges:

BranchAffectedCVEsVendor-recommended action
PowerSYSTEM Center 20205.29.x and earlierCVE-2026-63017Update to 2020 Update 30
PowerSYSTEM Center 20246.0.x to 6.2.xBothUpgrade to 2026 Update 1.1
PowerSYSTEM Center 20267.0.x to 7.1.xBothUpdate to 2026 Update 1.1

One inconsistency to note: the per-CVE sections of the CISA page also list the 2020 branch as “known_affected” under CVE-2026-63774, while the summary attributes only CVE-2026-63017 to that branch. Until the vendor clarifies, 2020-branch users should treat both flaws as applicable (our assessment).

Mitigations if you cannot patch yet

Subnet Solutions’ interim guidance, as relayed by CISA:

  • For CVE-2026-63017: monitor user activity records to confirm users are following acceptable-use policies, and disable the ability of Client Access Server users to open the browser’s F12 Developer Tools.
  • For CVE-2026-63774: disable user access to the report designer.

The vendor’s support contact for upgrade assistance is listed in the advisory.

What this means for operators

CISA lists the energy and critical manufacturing sectors for this product. A SQL injection reachable by any low-privileged account matters most where such accounts are broadly issued or shared, which is common in operational environments. Our assessment is that the practical priorities are:

  1. Inventory first. Identify every PowerSYSTEM Center instance and its branch and version. The advisory points 2024-branch users to 2026 Update 1.1 and names no fix within the 2024 branch, so in our reading those sites face a larger upgrade.
  2. Review accounts. List who holds accounts on the application and remove stale or shared credentials. Both flaws need authentication, so account hygiene directly reduces exposure.
  3. Restrict report designer access to named engineers until patched.
  4. Segment. Keep the application servers off general corporate and vendor-access networks. CISA’s standard guidance applies: minimise network exposure, place control system networks behind firewalls, and use up-to-date VPNs for remote access.
  5. Watch the audit trail. Unexpected report-designer sessions or unusual query activity from non-administrator accounts are worth alerting on.

Exploitation status

CISA reports that no known public exploitation specifically targeting these vulnerabilities had been reported to it as of the advisory’s publication on 3 November 2026. We found no other exploitation reports in the sources we checked on 4 November 2026 (the CISA advisory feed and the CISA Known Exploited Vulnerabilities catalogue).

CISA credits Chinmay Patel of Digital Boundary Group with reporting the vulnerabilities, and states that Subnet Solutions also reported them.