Overview

CISA released advisory ICSA-26-323-01 on 19 November 2026 for Autonomy Logic’s OpenPLC Runtime, an open-source soft PLC runtime used to run IEC 61131-3 control logic on commodity hardware. The flaw, CVE-2026-126088, is a race condition (CWE-362) in user creation. It affects versions up to and including 4.2.4.

The flaw

CISA describes the issue generically: concurrent requests pass the existence check before any user is committed, creating several unauthenticated administrator accounts. The vendor’s own fix pull request (Autonomy-Logic/openplc-runtime, PR #214) narrows the scope: the race is in the first-user bootstrap path of /api/create-user, and concurrent callers could become administrators alongside the legitimate operator on a factory-fresh or recently reset device. The vendor says it reproduced the bug on 4.2.4. That scoping comes from the vendor PR, not from CISA, and we have not reproduced it.

Our assessment: the exposure is a device that is newly installed, factory-reset or has an empty user table, and is reachable before the legitimate operator finishes setup. On the vendor’s description it is not a standing risk on a device that already has users. Race conditions need precise timing, hence high attack complexity.

Scores

VersionVectorScore
CVSS 3.1AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H8.1
CVSS 4.0AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H9.2

At the time of writing NVD lists the record as “Received”, so NVD has not added its own analysis. The scores above are those in CISA’s advisory.

Affected and fixed

  • Affected: OpenPLC Runtime 4.2.4 and earlier.
  • Fixed: OpenPLC Runtime 4.3.0 or later, per CISA. The vendor’s 4.3.0 release notes say first-admin bootstrap is now serialized to close a time-of-check/time-of-use race. 4.3.2 (2 November) is the current release as of our check.
  • Credit: reported to CISA by Noureddin Lutfi.
  • Sectors named by CISA: Critical Manufacturing, Energy, Transportation Systems, Water and Wastewater.

Exploitation status

CISA states: “No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.” The CISA KEV feed dated 18 November predates the advisory, so it says nothing either way.

Why it matters on a control network

An administrator on the OpenPLC web interface can typically change what logic the runtime executes. Our assessment: access to that interface is a path to altering process behaviour, not just to reading data, so the exposure belongs in the same bucket as an exposed engineering workstation. We have not tested this specific flaw, and CISA’s advisory does not describe post-exploitation behaviour.

What to do

  1. Upgrade to OpenPLC Runtime 4.3.0 or later.
  2. Until then, remove the web interface from any network path an untrusted party can reach. Do not expose control system devices to the internet.
  3. Place control networks and remote devices behind firewalls and isolate them from business networks.
  4. If remote access is unavoidable, use a current VPN, recognising that a VPN is only as secure as the devices connected to it.
  5. (Our recommendation, not from CISA.) Check devices that were reset or reinstalled, and audit OpenPLC user lists for unexpected administrator accounts alongside the operator’s. The same audit can confirm the 4.3.0 upgrade.
  6. Run an impact analysis and risk assessment before applying defensive measures, as CISA advises.

CISA also points to its ICS defence-in-depth recommended practices and to ICS-TIP-12-146-01B on targeted intrusion detection and mitigation.

Practical notes for asset owners

OpenPLC is often found in labs, pilots, small installations and as a teaching platform, which means instances sometimes sit outside formal asset inventories. Our assessment: before patching, find them. Search for hosts serving the OpenPLC web interface on your internal ranges, and for engineering laptops that run it locally. Where the web interface must stay reachable for engineers, restrict it to a management VLAN or jump host, and log every administrative session. Confirm the version from the interface or the install directory, and record the upgrade to 4.3.0 against each asset so that the fix is auditable.

Note that the advisory lists four sectors because OpenPLC is general-purpose. It does not mean each sector has a known affected deployment.

Detection ideas

There is no vendor-published detection. Our untested suggestion: if the runtime or a reverse proxy logs account creation, alert on more than one new user within a short window, and on any new administrator that was not created by a known administrator session.

Source: CISA ICS advisory ICSA-26-323-01, released 19 November 2026.

Tags
OpenPLCAutonomy LogicCVE-2026-126088CWE-362CISAICSA-26-323-01PLC