Overview

On 17 November 2026 CISA published ICSA-26-321-01 for Dorsett Controls InfoScan. The advisory covers InfoScan 1.45.0 and earlier and lists six CVEs: CVE-2026-117659, CVE-2026-120157, CVE-2026-120255, CVE-2026-120260, CVE-2026-120271 and CVE-2026-120298. CISA tags the critical infrastructure sector as Water and Wastewater Systems, deployed worldwide, with the vendor headquartered in the United States. Cyber-Tim reported the flaws to CISA.

CISA’s page headline says “5 Vulnerabilities”; that counts weakness types (CWE-497 appears twice). The advisory covers six CVEs across five weakness types.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA, according to the advisory. None of the six CVEs is in the CISA KEV catalog as of 2026-11-18.

The six vulnerabilities

Scores as published by CISA. The page does not say who assigned them.

CVECWECVSS v3.1CVSS v4.0What it is
CVE-2026-117659295 Improper Certificate Validation8.18.5Electron client accepts untrusted TLS certificates
CVE-2026-120157497 Sensitive System Information Exposure5.36.9Installer contains customer and internal hostnames
CVE-2026-120255321 Hard-coded Cryptographic Key4.35.1Fixed key and IV protect the MongoDB password in the registry
CVE-2026-120260306 Missing Authentication5.56.8Unauthenticated template endpoint
CVE-2026-120271497 Sensitive System Information Exposure5.36.9Unauthenticated system information disclosure
CVE-2026-120298209 Error Message with Sensitive Information5.36.9Node.js stack traces from login and password-reset endpoints

The advisory’s headline CVSS (vendor equipment, v3) is 8.1, which is the CVE-2026-117659 score.

CVE-2026-117659: the one that matters

CISA says the InfoScan Electron desktop client “improperly handles TLS certificate errors by accepting certificates without validating their trustworthiness.” The client also runs Electron with nodeIntegration enabled, contextIsolation disabled and webSecurity disabled, settings that, in CISA’s words, weaken the client’s security boundaries. An attacker who can intercept or manipulate network communications may present an untrusted certificate without the application rejecting the connection.

The v3.1 vector is AV:N/AC:L/PR:N/UI:R, high confidentiality and integrity impact, no availability impact.

Our assessment (not CISA text): an attacker positioned on the path between an operator workstation and the InfoScan server could impersonate the server and capture credentials or tamper with data. The advisory does not describe code execution, so we do not claim it.

Information disclosure cluster

The other five CVEs are lower rated but useful for reconnaissance.

  • CVE-2026-120271. Unauthenticated requests to mobile-enumeration and version-reporting endpoints return usernames and display names, multifactor authentication configuration status, session settings, application and server version information, hardware module firmware versions, and the BACnet/IP port used by the installation. The BACnet/IP detail is the OT-relevant part: it tells a remote attacker where the building automation protocol is listening.
  • CVE-2026-120157. The public Electron installer carries configuration files with hostnames tied to customer installations and to internal development, test and database infrastructure. No authentication is needed to extract them.
  • CVE-2026-120255. InfoScan uses hard-coded cryptographic keys and initialization vectors to encrypt the MongoDB password before storing it in the Windows registry. Someone with the registry value and the application code may recover the database password.
  • CVE-2026-120260. An endpoint that returns sales-automation templates does not enforce authentication. CISA says “a local attacker can submit an HTTP request” (AV:L).
  • CVE-2026-120298. Malformed requests to the login and password-reset endpoints trigger unhandled exceptions that return Node.js stack traces, disclosing filesystem paths, directory names, source file locations and line numbers.

Remediation

Dorsett Controls recommends updating InfoScan to v1.46 or higher. Per the advisory, administrators log in to InfoScan, open System Maintenance, select Check for Updates and click Install Now in the Ready To Install section. Offline customers download the update from the Dorsett Controls Customer Portal (InfoScan Update tile) and follow the instructions there.

CISA’s general guidance applies: keep control systems off the internet, behind firewalls and isolated from business networks.

What to do now

Our recommendations, based on the advisory:

  1. Inventory InfoScan installs. 1.45.0 or earlier is affected.
  2. Patch to v1.46 or later; plan the offline route for isolated sites.
  3. Until patched, keep InfoScan off untrusted networks and do not run the Electron client across segments an attacker could intercept.
  4. Check whether InfoScan web endpoints are reachable from outside the management network. The unauthenticated disclosure endpoints are only a problem if someone can reach them.
  5. After patching, consider rotating the MongoDB credential, since the old one was protected by a key that is public in the application. This is our judgement; the advisory does not say it.

Unverified and limits

  • CVE records and NVD entries were not yet available when checked on 2026-11-18 (NVD returned no results for all six; CVE.org returned no record for CVE-2026-117659). The scores come only from CISA’s advisory page.
  • We did not open a Dorsett Controls vendor advisory; fix details are from CISA’s advisory.
  • We do not know how many water utilities run InfoScan.

References

Tags
Dorsett ControlsInfoScanElectronTLSBACnet/IPCWE-295CWE-321ICSA-26-321-01